Molded Case Circuit Breaker, 800, 600VAC, 3 Pole, I-Line Bracket Mounting Style

  • Square D
  • Molded Case Circuit Breaker 600V 800A

    graingerSKU: , mscSKU: , zoro_no: G0842077, mongo_id: 65bbe7053aaddbd5a906b7e9

Web Price
$7,439.99 / each
Qty

Product Details

600VAC
-13 to 158°F (-25 to 70°C)
-58 to 185°F (-50 to 85°C)
800
HACR rated Applications; Distribution
3 x AWG 3/0 to 3 x 500 kcmil aluminium/copper
AIR 65 kA 240 V AC 50/60 Hz UL 489; AIR 35 kA 480 V AC 50/60 Hz UL 489; AIR 18 kA 600 V AC 50/60 Hz UL 489; Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2; Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
G
Operating Handle
HACR rated
I-Line Bracket
Black
0.8
United States
8.05 in
Distribution
I-Line connection, line; Lugs, load
Mercury Free; PVC Free
M
12.86 in
1600 to 8000 A
25 kA at 240V AC, 20 kA at 380/415V AC, 65 kA at 240V AC, 35 kA at 380/415/480V AC, 18 kA at 600V AC, 50 kA at 240V AC
IP40
800 A
1 trip indicator green)
300 to 800 A
65 kA
(3) 500 kcmil (Cu/Al)
(3) 3/0 AWG (Cu/Al)
9 in (228.60 mm)
I-Line bracket)
Bracket
50/60 Hz
3
2 auxiliary switch OF plug-in; 1 alarm switch SD plug-in; 1 voltage release MN or MX plug-in)
Less than 6561.68 ft (2000 m) without derating; 13123.36 ft (4000 m) with derating
1
AC
3 IEC 60947-1
0.98 in (25 mm)
UL; CSA; NOM
PowerPact M
Circuit breaker
CE
8 kV IEC 60947-2
750 V IEC 60947-2
600 V AC 50/60 Hz UL 489
25 kA 240 V AC 50/60 Hz IEC 60947-2; 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
UL, CSA, NEMA, NOM, CE
Yes IEC 60947-2
I-Line, Lug
AL800M23K
442.54 lbf.in (50 N.m) 0.15 to 0.37 in² (95 to 240 mm²) (3 x AWG 3/0 to 3 x 500 kcmil)
Electronic
ET 1.0
Electronic, basic, ET 1.0,
Category A
8.27 in

Viewed together

Benchstand Belt, Coated, 6 in W, 48 in L, 50 Grit, Coarse, Ceramic, Predator, Yellow
$30.36 / each
Web price